Tuesday, September 20, 2011

600GF1-RT Natural gas generator

1.Output:30kw~600kw,50/60Hz
2.ISO9001,CE
3.one year or1500hours warranty
4.Long relationship with siemens,wood,Veolia
1.
600GF1-RT

Technical specification
a.Technical specification of gas generator set
Mode
600GF1-RT
Engine model
T12V190Z
L
-2A
Generator model
1FC6 454-6LA42-Z
Control panel model
PCK1-RB600
Rated power kw
600
Rated current A
1086
Rated voltage V
400
Rated power factor, COSΦ
0.8(lagging)
Frequency(Hz)
50
Starting method
24V DC motor starting
Voltage regulation
Automatic voltage regulation
Governing Method
Electronic Governing
Exciting method
Brushless
Phase and wiring
Three-phase, four-Wire system
Connecting Method between engine and generator
Flexible coupling
Cooling method of water cycle
Open (with heat exchanger)
Dimensions (l×b×h),mm
5357×1970×2690
Weight kg
12500
b.
Technical specification of control panel
Model
PCK1-RB600
PCK1-RZ600
Functions
The PCK1-RB600 control panel has comprehensive protecting function for over-current, short circuit, reverse power, low frequency and low voltage etc.
It also has the functions of semiautomatic quasi-synchronism, automatic power factor adjustment.
PCK1-RB600 can also cooperate with TEM system and monitoring instrument, to monitor water temp, oil temp, oil pressure and speed of the engine. Once threat emerges, control panel will alarm and automatically switch off for protection.
The PCK1-RZ600 control panel has comprehensive protecting function for over-current, short circuit, reverse power, low frequency and low voltage etc.
It also has the functions of automatic quasi-synchronism, load distribution and automatic power factor adjustment.
PCK1-RZ600 can analyze the condition of the grid, once the grid is shut down, it can cut the gas generator set from the grid until the grid start to work again, then automatically recover the connection.
The control panel can also cooperate with TEM system and monitoring instrument, to monitor water temp, oil temp, oil pressure and speed of the engine. Once threat emerges, control panel will alarm and automatically switch off for protection.
Application method
Work with grid connection or single unit operation
Work with grid connection or single unit operation or parallel operation
Dimension
L×H×W
mm×mm×mm
800×1000×2200
2.Operating requirement
a.Ambient conditions
1)Ambient temperature : -40°c~40°c
2)Relative humidity≤95%(35°c)
3)ASL Above Sea Level≤2000m
4)Working atmosphere: flashing board