Saturday, August 20, 2011

Cummins 100KW Diesel Generator Set Hot

100KW Diesel Generator Set Cummins engine
1. Certificate: CE & ISO
2. warranty:1 YEAR
3.OEM service offered
1.
Name:
100KW Cummins Diesel Generator Set

2.
ENGINE DATA
Manufacturer / Model
DCEC Cummins 6BTA5.9-G ,4-cycle
Air Intake System
Turbo,Water/Air Cooling
Fuel System
A type fuel pump
Cylinder Arrangement
6 in line
Displacement
5.9L
Bore and Stroke
102×120(mm)
Compression Ratio
17/1
Rated RPM
1500rpm

Max. Standby Power at Rated RPM
116KW/157HP
Governor Type
Electronic

3
.
Alternator Data
Manufacturer
Stamford/ Leroy Somer etc
Number of Phase
3
Connecting Type
3 Phase and 4 Wires, “Y” type connecting
Number of Bearing
1
Power Factor
0.8
Protection Grade
IP23
Altitude
≤1000m
Exciter Type
Brushless, self-exciting
Insulation Class, Temperature Rise
H/H
Telephone Influence Factor (TIF)
<50
THF
<2%
Voltage Regulation, Steady State
≤±1%
Alternator Capacity
120KVA
Alternator Efficiencies
90.6%
Air Cooling Flow
0.514m3/s

4.GENERATING SET DATA
Voltage Regulation
≥±5%
Voltage Regulation, Stead State
≤±1%
Sudden Voltage Warp (100% Sudden Reduce)
≤+25%
Sudden Voltage Warp (Sudden Increase)
≤-20%
Voltage Stable Time (100% Sudden Reduce)
≤6S
Voltage Stable Time (Sudden Increase)
≤6S
Frequency Regulation, Stead State
≤5%
Frequency Waving
≤0.5%
Sudden Frequency Warp (100% Sudden Reduce)
≤+12%
Sudden Frequency Warp (Sudden Increase)
≤-10%
Frequency Recovery Time (100% Sudden Reduce)
≤5S
Frequency Recovery Time (Sudden Increase)
≤5S

5.Operation
After diesel generator installed, you can put into power, before each start, at least the following items should be checked
1.whether unit surface and around has debris
2.keep the into and exhaust channel of the engine room is smooth
3.the cooling liquid tank is normal
4.the air filter indicator directs normal
5.lubricating oil level is within normal range
6.the fuel valve is open, the supply of fuel to engine is normal
7.battery cables are connected correctly
8.power load device is ready
,when the generator directly with the load, breaking the air switch before start.

No comments: